Intelligent valve electric device static loss and motion loss stage causes and processes

Publish Time: 2024-06-17

The loss phase is divided into static and motion. In the "local control" mode, the intelligent valve electric device can be operated; if the "loss phase" appears immediately, it is a static loss phase or the "loss phase" appears after 1 to 2 seconds, which is a motion loss phase.


Causes and processes of static loss phase


Cause 1: One phase of the three-phase power supply of the actuator is lost; Step 1: Check the voltage of the actuator terminal box and eliminate the loss phase. Cause 2: Volatility of the connecting rod in the actuator; Step 2: Reconnect the link in the actuator. Cause 3: The components on the power board of the actuator are damaged; Step 3: Replace the power board in the actuator.


Causes and processes of motion loss phase


Cause 1: Volatility of the connecting rod in the actuator; Step 1: Reconnect the connecting rod in the actuator. Cause 2: The AC contactor in the actuator is damaged; Step 2: Replace the AC contactor in the actuator. Cause 3: The motor in the actuator is damaged; Step 3: Replace the motor in the actuator. Cause 4: The components on the power board of the actuator are damaged; Step 4: Replace the power board in the actuator.

×